Reactors

Nova

Nova reactors are an efficient and effective solution to address both line-side and load-side issues associated with demanding drive applications. They deliver protection for motors and AC drives while minimizing system harmonics.  Benefits include reduced line notching, extended life of switching components and motors, reduced audible motor noise and operating temperature, mitigation of nuisance tripping, and minimization of harmonic distortion.

They are available in standard ratings from 0.5 HP (373 Watts) to 250 HP (745 kilowatts), up to 600 V (690 V with de-rating) and are fully compliant with UL, CSA, CE, IEC, and NEMA standards.


Electrical reactor
  • System Voltage Ratings: 480 V, 600 V (690 V de-rated)
  • Frequency: 50 / 60  Hz
  • Insulation system: 70ºC rise over average 50°C ambient for 130ºC Temperature Class 115ºC rise over average 50°C ambient for 180ºC and 220ºC Temperature Classes
  • Typical impedance: 1.5%, 3% to 5%
  • Altitude (de-rating): Comply with NEMA ST20
  • Inductance Tolerance: +15/-10%
  • Inductance Curve [% Nominal Inductance (L) @ % Rated Current (l)]: 100% at 100% Current; 95% at 110% Current; 80% at 150% Current; 50% at 200% Current
  • Dielectric strength to ground: 4000 volts for 1 minute or equivalent
  • Enclosure type: Type 1 (Type 3R available upon request)
  • Cooling Method: Natural convection
  • Certification: UL 508 - CSA C9 - CSA C22.2 No. 47 standards - CE Mark (IEC 61558-2-20:2000) UL Listed (up to 600V), file No. E61431 - CSA Certified file No. LR3902 - IEC 61558-2-20
  • Warranty: 10 year limited warranty